Product Details:

  • Power 50 - 500 Ampere (amp)
  • Ambient Temperature 0 to 48 Celsius (oC)
  • Suitable For Industrial Application
  • Product Type Electric Charger
  • Material Copper
  • Output Voltage As per requirement
  • Usage Battery
  • Click to View more
X

Industrial Battery Charger Price And Quantity

  • 01 Unit
  • 95000 INR/Unit

Industrial Battery Charger Product Specifications

  • Battery
  • 415 +-15% VOLT
  • 0 to 48 Celsius (oC)
  • 50 - 500 Ampere (amp)
  • Industrial Application
  • As per requirement
  • Electric Charger
  • Customized
  • 50 Hertz (HZ)
  • Copper
  • 12 Month

Industrial Battery Charger Trade Information

  • 10 Unit Per Month
  • 30 Days
  • All India

Product Description

Key Features

  • The capability to apply improved charging algorithms to reduce battery water consumption, thereby reducing user maintenance costs.
  • The potential to provide a multi-profile charger capability.
  • Automatic start when a battery is connected and disconnection when the battery is fully charged.
  • Increased product reliability, and reductions in circuit board size and cost.

Product Type - Electric Battery Charger

Usage - Battery Charging

Technical Specifications Of Industrial Battery Charger

Rating (Amp) As per customer requirement ( Custom make products )
Cooling Natural Air Cooled
AC input voltage 415V AC, 3 Phase, 4 Wire. Permissible variation +-10 %
AC input frequency 50 Hz. permissible variations: +2.5 HZ to -3HZ
DC output voltage 110V, 220V , 415V , 440V,650V
Current Limit ADJ. 80% - 100%
Power Conversion AC to DC by means of a three phase full wave
  Full controlled rectifier consisting of Thyristors/IGBT
Output voltage Regulation +-1% of set value for a frequency variation of +-2.5 HZ of input frequency, 
  +-10 % input voltage variations & a combined voltage & frequency (absolute
  sum) variation
  of 10%, 0-100% of load variations.
Efficiency % 85  90 % at FULL LOAD (At max. Voltage & Current)
Ripple voltage % 1 % PEAK TO PEAK without battery connected.
Switchgear:  
a) Input side SWITCH+FUSE+MCCB
b) Output Side MCCB+ SWITCH+FUSE+ MCCB
Protection (a)Surge suppressors (b)Soft start (c)Rectifier protection fuses
  (d)HRC fuses (e )Control circuit & Voltmeter fuses
Meters 96 X 96 Sq. mm. analogue meters;-
  Input voltmeter Output
  Voltmeter Output Ammeter
Indications: INPUT ON LAMPS, OUTPUT ON ,
  LAMP Charger ON, Float LED Charger
  ON Boost LED
Alarms MAINS FAIL
  OUTPUT UNDER VOLTAGE OUTPUT
  OVER VOLTAGE CHARGER FAIL
  OVER LOAD GROUND
  FAULT
  CHARGER TRIP
Operating Temperature 0- 50 degree centigrade
Protection Grade Suitable for Outdoor / Indoor Installation (IP 65 )
Insulation class Class F Limited to Class B
Insulation Break down 2.5KV per min
voltage  
Cables 1100 V grade PVC insulated copper cables are Used.
Average winding 70C above ambient temp,
temp. Rise over  
ambient  